Electrical Equipment Reliability with Ultrasound & Infrared

Ultrasound and infrared technologies are a perfect match when conducting inspections of electrical equipment.

Teilen:

Facebook
Twitter
LinkedIn
WhatsApp

Typical electrical components that can be inspected with ultrasound and infrared include switchgear, load interrupter switches, breakers, transformers, motor control centers, and terminal transition cabinets.

One electrical anomaly that ultrasound will detect is corona. Even though corona produces little to no heat, it does however produce ultrasonic emissions. If the inspector’s ultrasound instrument has on-board sound recording capability, the ultrasound emission from corona can be recorded and further analyzed for a correct diagnosis. A note of importance on corona is the fact that it is only present in voltage above 1000 volts. At 1000 volts and greater, air becomes a conductor and hence the ionization of air surrounding a connection can occur.

When the recorded ultrasound of corona is looked at in a spectrum analysis software, very prominent 60Hz harmonics can be noted. If the sound recording is done outside of North America, one would see very dominant 50Hz harmonics. Additionally, in between the 60Hz harmonics, you would see what is referred to as frequency content. Frequency content is basically harmonic activity between the more dominant harmonics. As the condition worsens, there will be a loss of the dominant 60Hz harmonics, and uniformity in the amplitude of the recorded ultrasound will decrease.
Tracking occurs when there is a low current pathway to ground across an insulator. Many will refer to tracking as “baby-arcing.” This event is common where there is severe breakdown of the insulating material and loose connections. Tracking can occur in low, mid, and high voltages and characterized as a steady buzzing sound with periodic “crackling” and “popping” sounds. Further damage is done when tracking is not corrected, and will rather quickly lead to arcing. Finally, arcing happens when there is a discharge to ground across an insulator.

Kontaktinformation

Kontaktieren Sie uns

Scroll to Top

Einladung zum Live-Webinar

Warum lohnt sich für Sie als ausstellendes Unternehmen eine Teilnahme an der PUMPS & VALVES Dortmund besonders? Lassen Sie sich kurz und knackig von den Vorteilen Ihrer Teilnahme überzeugen.

Stay connected.

PUMPS & VALVES Dortmund Newsletter

* required

By registering, you hereby agree that Easyfairs Deutschland GmbH and its affiliated companies can process your data for advertising purposes and therefore contact you, for example, by email, post or telephone. You can revoke your declaration of consent at any time with immediate effect. For further information please refer to our data privacy policy.